Directions for Use:
CK CWT is dosed into the expansion tank. The dosage amount is determined by monitoring the nitrite level in the water. The ideal nitrite concentration in the main machine water is 1,000–2,000 ppm. Adding 1 kg of CK CWT per metric ton of water will increase the nitrite reserve in the system by 75 ppm.
Recommended Values for Main Machine Water:
Chloride: max. 50 ppm
pH : 8.2 – 10
Nitrite: 1,000–2,000 ppm
If the water parameters in your system are not within the recommended range, they should be brought within the recommended range by performing a partial blowdown and adding CK CWT to the system.
Physical Characteristics:
Appearance: Light yellow / colorless liquid
Density: 1.03 – 1.13g/cm³ (at 20 °C)
pH: 11 – 13 (at 20 °C)
Flash Point: None
Corrosive Effect: May have corrosive effects upon prolonged contact with sensitive metal surfaces.