CK CWT EXTRA is dosed into the expansion tank. The dosage amount is determined by monitoring the nitrite level in the water. The ideal nitrite concentration in the main machine water is 1,000–2,000 ppm. Adding 1 kg of CK CWT EXTRA per metric ton of water will increase the nitrite reserve in the system by 150 ppm.
Recommended Values for Main Tank Water:
Chloride: max. 50 ppm
pH : 8.2 – 10
Nitrite : 1000 – 2000 ppm
If the water parameters in your system are not within the recommended range, you should perform a partial blowdown and add CK CWT EXTRA to the system to bring the parameters within the recommended range.
Physical Properties:
Appearance : Yellow, clear liquid
Density : 1.15 – 1.25g/cm³
pH : 11 – 13
Flash Point : None
Corrosive Effect : None