Directions for Use:
CK – CWP is dosed into the expansion tank in powder form. The dosage amount is determined by monitoring the nitrite level in the water. The ideal nitrite level in the main machine water is 1,000–2,000 ppm. Adding 1 kg of CK–CWP per metric ton of water will increase the nitrite reserve in the system by 1,000 ppm.
Recommended Values for Main Tank Water:
Chloride: max. 50 ppm
pH : 8.2 – 10
Nitrite : 1000 – 2000 ppm
If the water parameters in your system are not within the recommended range, you should bring them within the recommended range by performing a partial blowdown and adding CK–CWP to the system.
Physical Properties:
Appearance : White powder
Density : 2.10 g/cm³
pH : 9
Flash Point : None
Corrosive Effect : None