Directions for Use:
CK BWT is dosed into the boiler suction line, the condensate tank, or directly into the boiler using a dosing pump. For a boiler that has not previously used water treatment chemicals, the initial dosage of CK–BWT is 400 grams per 1 metric ton of boiler water. Subsequently, 100–200 grams of CK–BWT are dosed for every 1 metric ton of feedwater.
Recommended Values for Main Machine Water:
P. Alkalinity : 100–300 ppm
pH : 9 – 10.5
Klorür : < 300 ppm
If the chloride and partial alkalinity levels are higher than recommended, the boiler should be bled.
Physical Characteristics:
Appearance: Light yellow liquid
Density: 1.00 – 1.10 g/cm³
pH: 7 – 9
Flash Point: None
Corrosive Effect: In its pure form, it may have a corrosive effect on all types of metal upon contact.