Directions for Use:
CK BOIL-C is dosed into the boiler suction line, the condensate tank, or directly into the boiler using a dosing pump. For a boiler that has not previously used a water treatment chemical, the initial dosage of CK – BOIL-C is 200 grams per 1 metric ton of boiler water. Subsequently, 50–100 grams of CK–BOIL-C is dosed for every 1 metric ton of feedwater. (Dosing rates are calculated assuming the boiler is fed with evaporator water. The hardness value is assumed to be 10 ppm. The CK–BOIL-C dosing amount varies depending on the quality of the feedwater.)
Kazan suyunda önerilen değerler:
P.Alkalinite : 100 – 300 ppm
pH : 9 – 10,5
Klorür : < 300 ppm
Klorür ve p.alkalinite değerleri önerilenden büyükse kazan blöf edilmelidir.
Buhar dönüş hatlarında önerilen değerler:
pH : 8,2 – 9
Physical Properties:
Appearance : Light yellow liquid
Density : 1.00 – 1.10 g/cm³
pH : 10.5 – 11.5
Flash Point : None
Corrosive Effect : When in direct contact in its pure form, it may have a corrosive effect on all types of metal.