Directions for Use:
It is added to the water already in the system. The amount of water already present
Adding up to 20% DEFROGEN M protects the system down to –6 °C
Adding up to 30% DEFROGEN M protects the system down to 14 °C
Adding up to 40% DEFROGEN M allows the system to operate down to –23 °C
Adding up to 50% DEFROGEN M allows the system to operate down to –35 °C
Adding up to 60% DEFROGEN M allows the system to operate down to –45 °C
% 70’i kadar DEFROGEN M eklenmesi, sistemi < – 50 °C’ye kadar
makes it secure.
For corrosion control, it is recommended to add an amount equivalent to at least 30% of the system volume.
If a different corrosion inhibitor has been used in the system, the system must be drained and flushed before adding DEFROGEN M. If no antifreeze or corrosion inhibitor has been used in the system previously, it is recommended to drain and flush the system before using DEFROGEN M.
DEFROGEN M should not be dosed into the system in its undiluted form. First, fill the system two-thirds full with water; then add DEFROGEN M and top it off with water.
The water used to dilute DEFROGEN M must not contain more than 100 ppm of chloride.
Protective clothing, gloves, goggles, and a mask must be worn during the procedure.
Check:
The DEFROGEN M concentration in the system should be checked once a year. The DEFROGEN M concentration should be checked whenever water is added to the system.
Concentration control for DEFROGEN M is performed by the Cemkimsan Water Treatment Consultant.
Physical Characteristics:
Appearance: Colorless liquid
Density: 1.02–1.12g/cm³ (20 °C)
pH: –
Flash Point: 111 °C
Corrosive Effect: In its pure form, prolonged contact with it can cause corrosion on any type of metal.